Table SAC:
Load and Current Harmonic Measurements
Steady State Limits for Voltage and Frequency
108V to 118V RMS, 393 to 407 Hz
Apply for 30 mins each test
No Test, Done so test numbers coincide
Voltage Distortion Spectrum
Requires Additional
Equipment
Voltage Distortion Factor 0.05
Normal Voltage Transients
Repetitive Normal Voltage Transient Test
Run transient for 30 mins
Normal Frequency Transients
Underfrequency Transients
Abnormal Steady State Limits for Voltage and Frequency
100V RMS to 125V RMS, 380 Hz to 420
Hz
Abnormal Voltage Transients
Abnormal Frequency Transients
Emergency Steady State Limits for Voltage and Frequency
104V to 122V RMS, 360 to 440 Hz
Apply for 30 mins each test
N/A to AC Utilization
Equipment
Power Failure (Single Phase)
No test, done so numbers coincide